Building fire equipment detection report is false, unture. In this inspection, the detection reports issued by detection agency are more or less false or unture. Some fire facilities lack assemblies, cannot operate properly, the fire hydrant pumps, spray pumps has no testing drainage installations, two sprinkler system pump adapter as designed, actually, only one installed; some fire facilities installation clearly not meet the requirements, fire pool has no fire intake, the end testing equipment assembly installation of the water sprinkler has errors.The original records, inspection reports are not standardized. Universally, the data in testing report is not accurate, not standardized, not rigorous, the recorded digital has no concrete measure unit, cannot effectively reflect the test results, or only use "meet the requirements" instead of specific data and device status.